Fluke 6100A Electrical Power Quality Calibrator

Condition:
Used
Test Standards:
IEC61000-3-3, IEC 61000-4-30, EN61010-1:2001, CAN/CSA 22.2 No 1010.1-92, UL61010A-1, EN61000-3-2:2000, MIL-PRF-28800 class 3, IEC 60364-4-443
Applications:
Flicker, Harmonics, Fluctuating Harmonics, Interharmonics, Dips and Swells
Voltage:
100 V to 240 V with up to 10 % fluctuations
Range of fundamental frequency:
16 Hz to 450 Hz
Frequency Accuracy:
50 ppm
Manufacturer:
Fluke
$2,295.00

 

SKU:
sku-F6100A-RE
Availability:

IN STOCK


Getting Started...

6100A Overview

The most accurate, comprehensive and flexible source of electrical power signals, the Fluke 6100A Fluke 6100A Electrical Power Quality Calibrator sets a new benchmark for accuracy in power standards. Voltage and current are generated with up to 6 digits resolution and accuracys approaching 100 ppm (0.01 %). Phase adjustment provides for 1 milli-degree or 10 micro-Radian resolution. Phase performance is exceptional, with accuracy to 3 milli-degrees and short term stability to 200 micro-degrees. In multi-phase systems phase accuracy between phases is 5 millidegrees, again with short term stability to 200 micro-degrees. This outstanding level of phase performance equals or exceeds a number of commercially available phase standards. Phase accuracy is imperative in achieving power accuracy. The 3 milli-degrees phase accuracy of the Fluke 6100A ensures power accuracy approaching 200 ppm (0.02 %) can be achieved. Simple trigonometry applied to the equation Power = VIcosø demonstrates that compromising phase performance can only severely degrade power uncertainty.

Fluke 6100A Electrical Power Quality Calibrator Specifications:

Primary specifications

Voltage/Current amplitude setting resolution: 6 digits
Range of fundamental frequency: 16 Hz to 450 Hz
Frequency accuracy: 50 ppm
Frequency setting resolution: 0.1 Hz
Time to full accuracy: 1 hour
Settling time: < 1.4 second
Nominal angle between voltage phases: 120 º
Nominal angle between voltage and current of a phase: 0 º
Phase angle setting: ± 180 º, ± π radians
Phase angle setting resolution: 0.001 º, 0.00001 radians

Harmonics

Number of harmonics available: 100 (simultaneously if required)
Maximum harmonic frequency available: 6 kHz (100th Harmonic of 60 Hz)
Maximum level of individual harmonic: 30 % of fundamental level
Setting Method (user selectable): % RMS, % fundamental, dB down from fundamental, absolute value

Flicker

Setting range: ±30 % of set voltage or current within range values (60 % ∆V/V)
Flicker modulation depth accuracy: 0.025 %
Modulation depth setting resolution: 0.001 %
Shape: Rectangular or Sinusoidal
Duty cycle (shape = rectangular): 0.1 % to 99.9 % ±31 µs
Modulating Frequency range: 0.0008 Hz to 40 Hz
Pst Indication accuracy: 0.25 % Valid for Voltage only between 220 V and 240 V

Fluctuating Harmonics

Number of harmonics to fluctuate: Any number from 0 to all set harmonics can fluctuate
Setting range: ±30 % of nominal harmonic voltage
Fluctuation accuracy: 0.025 %
Modulation depth setting resolution: 0.001 %
Shape: Rectangular or Sinusoidal
Duty cycle (shape = rectangular): 0.1 % to 99.9 % ±31 µs
Modulating Frequency range: 0.008 Hz to 30 Hz

Interharmonics

Frequency accuracy: 500 ppm
Amplitude accuracy 16 Hz to < 6 kHz: 1 %
Amplitude accuracy > 6 kHz: 4 %
Maximum value of a single interharmonic: Maximum value for an interharmonic < 2850 Hz is 30 % of range. See Extended specifications for frequencies>2850 Hz
Frequency range of interharmonics: 16 Hz to 9 kHz

Dips and swells

Dip/Swell Min duration: 0.5 cycles
Dip/Swell Max duration: 1 minute
Dip Min amplitude: 10 % of the nominal output
Swell Max amplitude: The lesser of full range value or 140 % of the nominal output
Ramp up/down period: Settable 100 µs to 30 seconds
Optional repeat with delay: 0 to 60 seconds ±31 µs
Starting level amplitude accuracy: ±0.25 % of level
Dip/Swell level amplitude accuracy: ±0.25 % of level
Trigger out: TTL falling edge coincident with start of Dip/Swell event remaining low for 10 µs to 31 µs

Power

Voltage: 100 V to 240 V with up to 10 % fluctuations
Transient overvoltages: Impulse withstand (overvoltage) category II of IEC 60364-4-443
Frequency: 47 Hz to 63 Hz
Max. consumption: 1000 VA 100 V – 130 V, 1250 VA 130 V – 240 V

Dimensions


Height: 233 mm (9.17 inches)
Width: 432 mm (17 inches)
Depth: 630 mm (24.8 inches)
Weight: 23 kg (51 lbs)

Environment

Operating temperature: 5 ºC to 40 ºC
Calibration temperature: 16 ºC to 30 ºC
Storage temperature: 0 ºC to 50 ºC
Transit temperature: -20 ºC to 60 ºC < 100 hours
Warm up time: 1 hour
Safe Operating Max. Relative Humidity (non-condensing): < 80 % 5 ºC to 31 ºC ramping linearly to 50 % at 40 ºC
Storage Max Relative Humidity (non-condensing): <95 % 0 ºC to 50 ºC
Operating altitude: 0 m to 2,000 m
Non operating altitude: 0 to 12,000 m
Shock: MIL-PRF-28800 class 3
Vibration: MIL-PRF-28800 class 3
Enclosure: MIL-PRF-28800 class 3

6100A Key Considerations

Manufacturer:
Fluke
Test Standards:
IEC61000-3-3, IEC 61000-4-30, EN61010-1:2001, CAN/CSA 22.2 No 1010.1-92, UL61010A-1, EN61000-3-2:2000, MIL-PRF-28800 class 3, IEC 60364-4-443
Applications:
Flicker, Harmonics, Fluctuating Harmonics, Interharmonics, Dips and Swells
Voltage:
100 V to 240 V with up to 10 % fluctuations
Range of fundamental frequency:
16 Hz to 450 Hz
Frequency Accuracy:
50 ppm

Connect with The EMC Shop