Haefely PCD 130 3 Phase Coupling/Decoupling Network for PSURGE 8000

Condition:
Used
Weight:
69 kg (net weight)
Combination wave pulse 1, 2/50 - 8/20 μs (Hybrid-Surge pulse):
Pulse conforms to IEC/EN 61000-4-5
Coupling:
3 Phase - 32 Amps, 690 VAC
Dimensions:
45 x 50 x 57 cm (W x H x D)
General Data:
Technical Details
Phase synchronization:
1° steps
Polarity:
pos / neg
Pulse current (short circuit):
32A RMS
Pulse voltage (open circuit):
690V RMS (Phase-Phase) 110V DC
Standards Met:
IEC 61000-4-5 Ed. 1 & 2 and ANSI C62.41 and C62.45
Manufacturer:
Haefely
Online Orders Ship Same Day

 

Availability:

In Stock

SKU:
sku-444

 

This product is available for shipping to North America and Western European countries.


Getting Started...

Check out our Google Reviews

Overview

Haefely PCD 130 Module Description:

IEC and EN standards cover testing of 3 phase AC and DC power ports. They include recommendations for the coupling and decoupling component values within the CDN. These values are largely based on the European model for AC power lines. PCD 130 includes all the IEC and EN requirements with automatic coupling path switching. PCD 130 EUT output has specially designed 4mm connectors, which provide enhanced personnel safety in relatio n to the high voltage impulse. ANSI / IEEE standards are the reference for power line tests in many American standards such as TIA - 968 - A (FCC part 68) and Telcordia (Bellcore) GR - 1089 - CORE . The ANSI standard contains much the same information as the IEC but based around the American experience with AC power lines. Impedance of the low voltage mains supply to earth is simulated by the addition of a 10 ohm resistor for IEC tests. ANSI has NO series resistor in the impulse path This difference comes from the practice in Europe of connecting ground to neutral at the distribution transformer, not the power service entry as in the USA. PCD 130 automatically sets the correct coupling elements for either IEC or ANSI as selected by the user. The integration in the WinFEAT&R control and reporting software package enhances an efficient set - up and operation of this test system. Most importantly, the test load can be transferred to a computer freeing valuable resources.

Benefits:

International application –Specifically designed to meet and exceed the requirem ents of IEC, EN, and ANSI tests for power line applications.

Synchronization path Switching – The PCD 130 synchronizes impulses with the selected coupling path.

Safe and Easy – The interlocked HV connections allow your operators to test safely and easily.

Full 32A capability – Both AC and DC loads up to 32A per phase can be connected through the PCD 130.

Sturdy and Reliable – Careful component selection ensures that the PCD 130 will continue to operate under the most strenuous testing regime.

Faster completion of testing program – The PCD 130 has 3 multiplexed inputs, enabling testing to continue with other pulses without having to remove power from the EUT.

Application:

  • Single & Three phase power line systems
  • IEC 61000-4-5 Edition 1 & 2 Power line testing
  • IEC 61000-4-12 Power line testing
  • ANSI C62.41 & C62.45 Power lines
  • Many IEC & EN Product standards

Haefely PCD 130 Module Includes:

  • Qty. 1 PCD 130 CDN
  • Qty. 1 HAEFELY HIPOTRONICS Bus cable 1m
  • Qty. 1 Earth bonding cable 1m
  • Qty. 1 Earth bonding cable 0.25m
  • Qty. 1 10A Mains cable (country specific)
  • Qty. 1 User Manual

Accessories:

PIM 100
Combination Wave tester according to ANSI C62.41 and IEC 61000 - 4 - 5.
PIM 110
100kHz Ring wave tester according to ANSI C62.41 & IEC 61000-4-12
ADAPTERS
Single phase input & output adapters enable PCD 130 to be used for single phase applications
WinFEAT&R
Control and reporting software. Runs under windows 98, NT, ME, 2000, XP
Rack Mounting
Modules can be rack mounted for greater mechanical stability and mobility.

Videos

Key Considerations

Manufacturer:
Haefely
Weight:
69 kg (net weight)
Combination wave pulse 1, 2/50 - 8/20 μs (Hybrid-Surge pulse):
Pulse conforms to IEC/EN 61000-4-5
Coupling:
3 Phase - 32 Amps, 690 VAC
Dimensions:
45 x 50 x 57 cm (W x H x D)
General Data:
Technical Details
Phase synchronization:
1° steps
Polarity:
pos / neg
Pulse current (short circuit):
32A RMS
Pulse voltage (open circuit):
690V RMS (Phase-Phase) 110V DC
Standards Met:
IEC 61000-4-5 Ed. 1 & 2 and ANSI C62.41 and C62.45

Connect with The EMC Shop

Our experienced staff can help you with applications, purchase and rental options.