Overview
Schloder CWG 1526-10 10A Coupling Network Surge
With the coupling network CWG 1526 EMC-tests (immunity) on electrical equipment can be performed. Basic for these tests is the standard IEC 61000-4-5 (surge test for unshielded unsymmetrical interconnection lines).
The interference pulses of the Surge-Generator CWG 1500 are superposed to the interconnection lines of the EUT. Using the coupling switch the coupling paths can be selected.
Technical Data | |
Nominal voltage AC | max. 240 V / 50 Hz |
Nominal voltage DC | max. 120 V |
Nominal current IN | CWG 1526- 4: 2 x 4 A at TU= 40°Celsius CWG 1526-10: 2 x 10 A at TU= 40°Celsius |
Serial choke | 2 x 20 mH |
Coupling capacity C | 0,5 µF |
Serial resistance R | 40 ? |
Maximum pulse voltage 1,2/50 µs | 4.400 Volt |
Various coupling paths, selected by switch | D1 - D2; D1 - ground; D2 - ground |
High voltage (HV) input | Fischer HV-jack D105A039 |
Input coupling network | Laboratory jacks |
Output coupling network | Laboratory jacks |
Input electronic supply | IEC-plug, 230 V / 0,5 A on the rear |
Ground connector additional via jack | on the front and rear |
Operation temperature | 0 up to 40° Celsius |
Housing (H x W x D) | 150 x 225 x 360 mm (3HE; 42TE) |
Weight, approx. | 4,8 kg (CWG 1526-4): 10,4 kg (CWG 1526-10) |