Description
The CDN-M3-16A is a Coupling Decoupling Network for conducted immunity testing according to IEC 61000-4-6. The CDN-M3-16A is compliant with IEC 61000-4-6 Annex D2 and is designed to inject common mode disturbance signals in the frequency range from 150 kHz to 230 MHz into unscreened AC and DC power supply lines.
CDN-M3-16A Coupling & Decoupling Network Specifications
- Maximum supply voltage: 300V AC, 600V DC
- Maximum current: 16A
- Frequency range: 150 kHz – 230 MHz
- Maximum RF input power: 6.5W CW
- Maximum RF input voltage: 32 V
- Common mode impedance:
- 150 kHz – 24 MHz: 150 Ω ± 20 Ω
- 24 MHz – 80 MHz: 150 Ω + 60 Ω / – 45 Ω
- 80 MHz – 230 MHz: 150 Ω ± 60 Ω
- Voltage Division Ratio: 150 kHz – 80 MHz: 9.5 dB ± 1 dB
- 80 MHz – 230 MHz: 9.5 dB + 3 dB / – 2 dB
- RF input connector: N – female
- EUT / AE connectors: 4 mm banana safety jacks, 4mm slots in base plate for GND connection
- Housing material: powder coated aluminium, stainless steel base plate
- Dimensions: 12 x 6 x 6 inches
- Weight: 2.2 lbs